Instrumentation cable

ICON Base RE-2X(ST)YQY

LEONI ICON BASE PRO 60120 M1 OS
RE-2X(St)YQY-fl  /  RE-2X(St)YSWBY-fl

Product information

Brand                                            ICON BASE
Mechanical protection                  steel wire braid
Fire behaviour                              IEC 60332-1-2
                                                     IEC 60332-3-24 (Cat. C)

Max. Temperature in °C               90
Operating Voltage                        300

Description

Product - Construction                Single & Multi-Pair, XLPE-Insulation, Collective Screen, Armour, PVC-Sheath

Properties / Applications

Application_1 - General
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2 group II classified areas (IEC 60079-14); not allowed for direct connection to low impedance source, e.g. the public mains electricity supply. (Please note possible additional or special installation requirements of IEC 60079-14).

Application_2 - Installation
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; for direct burial. Indoor installation is allowed in areas where the construction product regulations (CPR) acc. to EN 50575 of fire class are not required. (Please note the relevant legal / local installation requirements)

Construction

Conductor                               plain annealed copper wire, stranded, size: 0.5 mm2

Insulation                                cross-linked polyethylene XLPE

Colour code                            black / white, continuously numbered on white core (1, 2, 3..) for multi-element

Collective screen                    aluminium polyester foil in contact with stranded tinned copper drain wire

Inner sheath                           polyvinyl chloride PVC, black

Armour                                   galvanised steel wire braid, opt. coverage 80% (min.)

Outer sheath                          polyvinyl chloride PVC, black, blue for intrinsically safe systems

Cable marking                       LEONI KERPEN ICON BASE Type Code Size 300V RP EN 50288-7 CE
                                              Production Lot Code Year Length Marking

Standards, certificates and approvals

Standard                               N 50288-7

Characteristics:

  • Low flammability
  • Oil and UV-resistant
  • Suitable for inside and outside installation
  • Usable in cable slots, trays, or conduits
  • Suitable for fitting aboveground
  • Safety certificate available

Stocklist

Size Color Diameter Copper Weight Product (code)
mmØ kg/km kg/km
0,75 mm²
1x2 Black 9.6 18 135 67540202
1x2 Blue 9.6 18 135 67540203
2x2 Black 12.7 33 220 67540402
2x2 Blue 12.7 33 220 67540403
4x2 Black 14.1 63 272 67540802
4x2 Blue 14.1 63 272 67540803
8x2 Black 17.5 123 430 67541602
12x2 Black 19.8 183 537 67542402
12x2 Blue 19.8 183 537 67542403
16x2 Black 22.3 243 680 67543202
16x2 Blue 22.3 243 680 67543203
24x2 Black 25.8 364 900 67544802
24x2 Blue 25.8 364 900 67544803
1,3 mm²
1x2 Black 17 29 169 67570202
1x2 Blue 17 29 169 67570203
1x3 Black 11.1 42 186 67570302
1x3 Blue 11.1 42 186 67570303



« Back to overview


We are happy to help
Call us: +31 45 571 8090
Mail us: info@voltec.nl